Heat Pump Doctors logo, South Auckland Heat Pump Services home page 0800 925 417

Toshiba heat pump error codes and flashing lights

Not every lamp lit up on a Toshiba is a fault. Here's how to tell the difference, and what to send Phil when it is one, anywhere in South Auckland.

The work
Fault-finding and repairs on heat pumps and air con, plus servicing
Phil
An electrician by trade, fixing heat pumps since 2012
Brands
Mitsubishi, Fujitsu, Panasonic, Daikin and the other main brands
Where
Manukau, Papatoetoe and Māngere down to Papakura, Drury and Beachlands
TOSHIBAOPERATIONTIMER
WHAT TO TELL PHILSOUTH AUCKLAND

Toshiba · light flashing · send it to Phil

Brand
Toshiba
Lights
which light, how many flashes
Model
off the side sticker

When your Toshiba shows a fault

Got a two-digit number on a Toshiba floor console, or lamps doing something odd on a wall unit? Around Manukau and South Auckland, Phil starts from what the unit is showing and the model.

A fair bit of what Toshiba lamps do is normal. The Timer lamp stays on after you switch off while the unit dries itself out, and the lamps can be dimmed right down so a running unit looks dead. Those are listed below.

When it is a fault, send Phil the code or what the lamps are doing, plus the model, and he'll take it from there.

How a Toshiba shows a fault

On a floor console, the fault comes up as a two-digit code on the display panel on the front of the unit.

Newer wall units like the Shorai Edge have small white icons for Wi-Fi, ECO, PURE and Timer, and a large circle on the right that glows blue in cooling and orange in heating. Older wall units have a row of lamps across the front for Hi Power, Filter, Pre-Def, Timer and Operation.

The wireless remote doesn't show fault codes in normal use. On a RAV high wall with a wired controller, the code shows on the controller and it's in the list below. For any other code on a remote or controller, send it to Phil with the model and he looks it up for that unit.

The model number

It’s on a sticker on the indoor unit. A photo of it is all Phil needs.

Send it to Phil

The code or the light count, the model and what the unit is doing. Ring 0800 925 417 or use the form below.

Toshiba fault signals

These are the fault codes Toshiba sets out for owners of floor consoles and RAV high walls. Most of the RAV codes point to a sensor, a board, a fan motor or the power supply, and Phil's an electrician by trade.

Floor consoles (RAS-U2FVG)

The code shows on the console's own display.

  • Two-digit code on the display

    The console has found a fault and stopped, and the two digits on the display say which one.

    Points to depends on the code, which Phil matches to the console's model

High-wall units with a wired controller (RAV range)

The operation lamp and the check icon on the controller blink, and the code shows on the controller.

  • E01Electrical

    The wired controller isn't set as the main one, or it isn't hearing anything back from the indoor unit.

    Points to the controller's setting, its cable or the indoor board

  • E02Electrical

    The controller can't get its signal through to the indoor unit.

    Points to the cable between them, the indoor board or the controller

  • E03Electrical

    The indoor unit isn't hearing from the controller or a network adapter.

    Points to the controller, a network adapter or the indoor board

  • E04Electrical

    The indoor and outdoor units have lost their data link.

    Points to the cable between the units, or the indoor or outdoor board

  • E10Electrical

    The two chips on the indoor board, the main one and the fan motor one, have stopped talking.

    Points to the indoor board

  • E18Electrical

    Where several indoor units share one controller, the main unit has lost touch with one of the others.

    Points to an indoor board or the link between the units

  • E31Electrical

    Inside the outdoor unit, the boards have lost their data link.

    Points to the outdoor board

  • F01Electrical

    One of the indoor coil sensors (TCJ) is showing a break or a short.

    Points to that coil sensor or the indoor board

  • F02Electrical

    The other indoor coil sensor (TC) is showing a break or a short.

    Points to that coil sensor or the indoor board

  • F04Electrical

    The sensor on the compressor's outlet pipe (TD) is showing a break or a short.

    Points to that sensor or the outdoor board

  • F06Electrical

    The outdoor coil or suction pipe sensor (TE or TS) is showing a break or a short.

    Points to those sensors or the outdoor board

  • F07Electrical

    The TL pipe sensor at the outdoor unit has come loose, come unplugged or shorted.

    Points to the TL sensor or its plug

  • F08Electrical

    The sensor that reads the outside air (TO) is showing a break or a short.

    Points to the outdoor air sensor or the outdoor board

  • F10Electrical

    The room air sensor at the indoor unit (TA) is showing a break or a short.

    Points to the room air sensor or the indoor board

  • F12Electrical

    The TS sensor on the suction pipe has come loose, come unplugged or shorted.

    Points to the TS sensor or its plug

  • F13Electrical

    The temperature sensor on the inverter's heat sink has a fault.

    Points to that sensor or the outdoor board

  • F15Electrical

    Readings from the TE and TS sensors don't add up, as if they've been swapped or wired the wrong way.

    Points to the TE and TS sensors or their wiring

  • F29Electrical

    The memory chip on the indoor board has a fault.

    Points to the indoor board

  • F31Electrical

    The memory chip on the outdoor board has a fault.

    Points to the outdoor board

  • H01Electrical

    The compressor has hit its current limit even at its lowest speed, or a short-circuit current has shown up.

    Points to the current-sensing circuit, the supply voltage or the compressor

  • H02

    The compressor has locked up.

    Points to a seized compressor, or the wiring and board that drive it

  • H03Electrical

    The circuit that measures current isn't reading right, or a phase is missing.

    Points to the current-sensing circuit or the outdoor board

  • H04

    The thermostat on the compressor case has tripped because the compressor is running too hot.

    Points to the case thermostat, or a problem in the gas circuit

  • H06

    Pressure on the low side has dropped too far, or the sensor watching it has a fault.

    Points to the pressure sensor or switch, the outdoor board, or the gas charge

  • L10Electrical

    A setting jumper on the outdoor board is in the wrong position.

    Points to the outdoor board

  • L29Electrical

    A fault elsewhere in the outdoor unit, such as a data link fault between its boards or an overheated heat sink.

    Points to the outdoor board or the inverter

  • L30Electrical

    Something wired into the unit's external input has triggered and stopped it.

    Points to an external device or its wiring to the board

  • L31Electrical

    On a three-phase supply, the phases are in the wrong order.

    Points to the supply wiring or the outdoor board

  • P01Electrical

    The indoor fan motor has tripped its own heat protection.

    Points to the indoor fan motor or the indoor board

  • P03

    The pipe coming off the compressor has got too hot.

    Points to the gas circuit, with low gas one of the causes

  • P04

    The high-pressure protection has tripped.

    Points to the high-pressure switch, airflow or the gas circuit

  • P05Electrical

    A phase is missing or the supply voltage is wrong.

    Points to the mains coming in, or the wiring that feeds the unit

  • P07Electrical

    The heat sink on the inverter has overheated.

    Points to the outdoor inverter, or airflow around the outdoor unit

  • P10

    Water has built up in the indoor unit because the drain is blocked or the float switch has tripped.

    Points to a blocked drain, the float switch and its wiring, or the indoor board

  • P12Electrical

    The indoor fan motor has drawn too much current or locked up.

    Points to the indoor fan motor or the indoor board

  • P15

    The unit has picked up signs of a gas leak.

    Points to the pipework and its joints

  • P19

    The indoor coil is going cold while it should be heating, which points to the 4-way valve.

    Points to the 4-way valve or the coil sensors

  • P20

    Pressure on the high side went too high and the unit stopped itself.

    Points to airflow or the gas circuit

  • P22Electrical

    The outdoor fan drive has seen too much current, or the fan has locked.

    Points to the outdoor fan motor or the outdoor board

  • P26Electrical

    The inverter saw what looked like a short circuit and shut itself down.

    Points to the inverter's switching parts, the outdoor board, its wiring or the compressor

  • P29Electrical

    The board can't tell where the compressor motor is in its turn.

    Points to the outdoor board or the compressor

Toshiba lamps that look like trouble but aren't

  • Timer lamp on after you switch off

    That's self-clean. After cooling or dry, the fan keeps going for about 30 minutes to dry the coil, with the Timer lamp on.

  • Timer lamp blinking after setting the timer

    The weekly timer didn't finish setting. Set it again and the blinking stops.

  • Lamps dark while it's running

    The brightness has been turned down or off. The unit is still working.

  • Quick blinks and three beeps

    The Operation lamp blinking fast for five seconds with three beeps means auto restart after a power cut has just been switched on.

Heat Pump Doctors logo

Heat Pump Doctors, in Manukau since 2012

South Auckland Heat Pump Services is Phil of Heat Pump Doctors. He’s been fixing heat pumps and air con across South Auckland since 2012, and he’s an electrician by trade.

We find the fault first, then tell you what it is and what it’ll take before any repair goes ahead.

More about us

Toshiba code questions

Something else? Ring 0800 925 417 or put it in the form.

My Toshiba remote shows 00 after I pressed CHECK. Is that a fault?

No. CHECK is used to set the remote to A or B, and it shows 00 while you do. It isn't a fault code.

Why does my Toshiba take a few minutes to blow warm air?

In heating it warms up for about five minutes first, and the fans stop while it defrosts. It also holds off for three minutes after it's switched on or restarted.

What should I send Phil for a Toshiba fault?

The model, and either the code on the display or which lamps are lit or flashing. A photo or a short video of the front panel does the job.

Send Phil your Toshiba code

The brand is already picked. Add the code or the light count, the model and your suburb, and Phil calls you back.

Call 0800 925 417

What helps Phil most

  • The brand and the model number, off the sticker on the side
  • Which light is flashing and how many times, or the code
  • What the unit is doing, and since when
  • A photo of the lights or the sticker

We’re open Monday to Friday 9am to 5pm, Saturday 9am to 4pm.

    Fields are required unless marked optional. Privacy policy