LG heat pump error codes and flashing lights
Count the blinks on an LG and you've got the code. This is what each code points to, for heat pumps around Manukau and South Auckland.
- The work
- Fault-finding and repairs on heat pumps and air con, plus servicing
- Phil
- An electrician by trade, fixing heat pumps since 2012
- Brands
- Mitsubishi, Fujitsu, Panasonic, Daikin and the other main brands
- Where
- Manukau, Papatoetoe and Māngere down to Papakura, Drury and Beachlands
LG · code CH05 · send it to Phil
- Brand
- LG
- Code
- CH05
- Model
- off the side sticker
When your LG shows a fault
When an LG wall unit in Manukau or South Auckland stops and starts blinking a lamp at the lower right, it's giving you a code. The number of blinks is the code, so five blinks is CH05.
Units with a screen or a wired controller show the CH number outright, and some LG models show a letter code like E0 or F4 instead.
Phil starts from that number and the model. Count the blinks on both lamps, then send him both numbers and the model off the side label.
Counting the lamps on an LG
When an LG wall unit finds a fault it stops, and a lamp near the lower right of the front blinks out a count that repeats about every two seconds.
Codes under 10 blink on one lamp, so five blinks is CH05. Bigger codes use both lamps, one for the tens and one for the ones, and it isn't always clear which lamp is which. Count both lamps and send Phil both numbers, and he'll work out the code for your model.
Floor units, cassettes and wired controllers show CH and the number on the screen. A short phone video of the lamps helps, and if the unit's on the LG ThinQ app, Smart Diagnosis in the app menu shows the code too.
The model number
LG puts the model and serial number on a label on the side of each unit, indoor and outdoor.
Send it to Phil
The code or the light count, the model and what the unit is doing. Ring 0800 925 417 or use the form below.
LG codes and the part behind each
Most LG codes point to a sensor, a board, a fan motor or the power supply, which is electrical work, and Phil's an electrician by trade.
CH00 to CH09
On a wall unit, one lamp blinks the number. Screens show CH and the number.
CH00Electrical
A general signal that the unit wants a look. A blip in the power can set it off.
Points to not tied to one part
CH01Electrical
The sensor that reads the room air at the indoor unit is showing a break or a short.
Points to the room air sensor, its plug or the indoor board
CH02Electrical
The sensor on the pipe going into the indoor coil has gone open or short.
Points to the indoor coil inlet sensor, its plug or the indoor board
CH04
Water from the unit isn't draining away and the tray is filling up. This one shows on ceiling and ducted units with a drain pump.
Points to a drain pump or float switch that's stopped working, or a blocked drain
CH05Electrical
The indoor unit has stopped hearing from the outdoor unit.
Points to the link wiring between the units, power to the outdoor unit, or either board
CH06Electrical
The sensor on the pipe coming out of the indoor coil has gone open or short.
Points to the indoor coil outlet sensor, its plug or the indoor board
CH09Electrical
The memory chip on the indoor board has a data fault.
Points to the indoor board
CH10 and up
On a wall unit, both lamps blink, one for each digit. Screens show CH and the number.
CH10Electrical
The indoor fan isn't turning. It's stuck, or the motor won't run. Some models show E6 for this.
Points to a seized or failed indoor fan motor, something caught in the fan, or the board that runs it
CH12Electrical
The sensor halfway along the indoor coil has gone open or short.
Points to the indoor mid-coil sensor, its plug or the indoor board
CH21Electrical
The outdoor unit saw a sudden spike in current and shut down to save its power module.
Points to the power module on the inverter board, the compressor, or an overload such as a blocked outdoor fan
CH22Electrical
The unit is pulling more current from the mains than it's allowed to.
Points to too much load on the outdoor unit or compressor, the inverter board, or the mains
CH23Electrical
Voltage on the DC side of the outdoor inverter has fallen below where it should be.
Points to the outdoor inverter board, or low mains voltage
CH25Electrical
The mains voltage coming in is too high or too low for the unit to run.
Points to the supply, a loose supply connection, or the voltage sensing on the outdoor board
CH26Electrical
The compressor won't start turning, or the board loses track of it once it does.
Points to a seized or failed compressor, its wiring, or the outdoor inverter board
CH27Electrical
Too much current is flowing through the power-factor stage in the outdoor unit.
Points to the outdoor inverter board
CH28Electrical
Voltage on the DC side that powers the compressor has climbed too high.
Points to the outdoor inverter board or the mains supply
CH29Electrical
The compressor is drawing more current than it should.
Points to the compressor, its wiring, the outdoor inverter board, or the unit working too hard
CH31Electrical
The unit's current sensor is giving a reading so low it can't be right.
Points to the current sensor or the outdoor board
CH32
The pipe coming off the compressor is running too hot.
Points to low gas, a blockage in the pipework, poor airflow outdoors, or the discharge sensor
CH33 / CH36
LG puts these two with gas and compressor faults, low gas most of all, without giving each number its own meaning.
Points to low gas, or the compressor, its drive or its protection
CH34
High pressure or overheating has stopped the unit, mostly down to poor airflow. Some models show this in place of CH61.
Points to a blocked filter or coil, or poor airflow around the outdoor unit
CH38
The unit has worked out it's short of gas. Some models show F4 for this.
Points to a gas leak or not enough gas, often at a pipe joint after the unit has been put in or moved
CH40Electrical
The circuit that senses current has gone open or short.
Points to the current sensor or the outdoor board
CH41Electrical
The sensor on the compressor's outlet pipe has gone open or short.
Points to the discharge pipe sensor, its plug or the outdoor board
CH42 / CH43 / CH47Electrical
These are sensor faults. On some models CH43 is the high-pressure sensor, and LG doesn't name the sensor for 42 or 47.
Points to a sensor for temperature or pressure, the plug it connects with, or the main board
CH44Electrical
The sensor that reads the outside air temperature has gone open or short.
Points to the outdoor air sensor, its plug or the outdoor board
CH45Electrical
The sensor halfway along the outdoor coil has gone open or short.
Points to the outdoor mid-coil sensor, its plug or the outdoor board
CH46Electrical
The sensor on the suction pipe at the outdoor unit has gone open or short.
Points to the suction pipe sensor, its plug or the outdoor board
CH48Electrical
The sensor on the outlet pipe of the outdoor coil has gone open or short.
Points to the liquid pipe sensor, its plug or the outdoor board
CH53Electrical
Signals from the indoor unit aren't reaching the outdoor unit properly.
Points to the link wiring, an unsteady supply, or either board
CH54Electrical
On a three-phase supply, the phases are in the wrong order or one is missing.
Points to the supply wiring, and it tends to follow a power cut or electrical work on the house
CH60Electrical
The memory chip on the outdoor board has failed its data check.
Points to the outdoor board
CH61
The outdoor coil is too hot in cooling, or the indoor coil in heating, so the unit stops to protect itself. It stays on until the power's been turned off and on, even once the cause is gone.
Points to poor airflow from a crowded outdoor unit, hot air going round again, or a dirty indoor filter in heating
CH62Electrical
The inverter board in the outdoor unit is overheating at its heat sink.
Points to cooling of the inverter board, the outdoor fan or airflow, or the board itself
CH63
The pipe on the outdoor coil has got too cold.
Points to gas or airflow at the outdoor coil, or the coil sensor
CH65Electrical
The temperature sensor on the inverter heat sink has gone open or short.
Points to the heat sink sensor or the outdoor inverter board
CH66Electrical
The indoor and outdoor units aren't matched up properly, in the wiring or the pipes. It tends to show up on a unit that has just gone in.
Points to wiring or pipes run to the wrong unit or port, or a brief fault on the supply
CH67Electrical
The outdoor fan is stuck or won't run. Some models show EF for this.
Points to a seized or failed outdoor fan motor, something caught in the fan, or the board that runs it
CH90 / CH91
A protective stop during the test run. On a unit that has just gone in it points to the pipework, and in normal use to a passing power problem.
Points to pipe connections or gas flow on a new setup, or the supply
CH92
LG puts this with setup and test-run problems and doesn't give it a meaning of its own.
Points to wiring, a test run that didn't finish, or restricted gas flow
CH93Electrical
The indoor and outdoor units can't talk, and it shows mostly at the test run. On some newer models it means the outdoor unit has no power.
Points to power to the outdoor unit, or the link cable connections
Letter codes on LG screens
Shown on units with a display or a wired controller.
E0Electrical
The indoor and outdoor units have lost touch, the same kind of fault as CH05 and CH53.
Points to the link wiring, an unsteady supply, or either board
E1, E2, E3, E7, E8, F2, F3Electrical
All sensor faults on LG models that use letter codes. LG doesn't tie each one to a particular sensor.
Points to one of the sensors on the air or pipework, the plug it connects with, the main board, or a short-lived electrical fault
E9Electrical
LG groups E9 with faults on the outdoor compressor and the electronics that drive it.
Points to the compressor, its drive or protection circuit, or the outdoor electrics
When an LG blinks or blows cold and nothing's wrong
Lamp blinks six or four times after holding the button
Holding the on/off button on the indoor unit for six seconds turns auto restart off (six blinks) or back on (four blinks).
18 minutes of strong cold air
Holding the on/off button on the indoor unit for three to five seconds starts a test run. It cools hard for 18 minutes, then goes back to its factory settings.
CH07 on a multi-room system
One room is set to heat and another to cool on the same outdoor unit. Set them all to heating, or all to cooling, and it clears.
E0 while power limiting is on
On some models E0 comes up while the kW Manager feature is holding power down. That's the feature working, not a fault.

Heat Pump Doctors, in Manukau since 2012
South Auckland Heat Pump Services is Phil of Heat Pump Doctors. He’s been fixing heat pumps and air con across South Auckland since 2012, and he’s an electrician by trade.
We find the fault first, then tell you what it is and what it’ll take before any repair goes ahead.
Other brands’ codes
- Mitsubishi ElectricBlink counts on the operation lamp, and P, E and U codes
- FujitsuOperation and Timer flashes that make a two-digit code
- PanasonicH and F codes behind a blinking timer light
- DaikinU, A, E, F and L codes, read with the remote
- HitachiTimer lamp blink counts
- ToshibaWhich lamps flash together, and how fast
- SamsungE and C codes on the indoor display
- HaierE and F codes on the two-digit display
- GreeE, F, H and L codes on the temperature display
- CarrierE, P and F codes in the display window
LG code questions
Something else? Ring 0800 925 417 or put it in the form.
My LG is blinking two lamps. Which number comes first?
It isn't always clear which lamp gives the tens, so count each lamp on its own and send Phil both numbers. He'll work out the code from the model.
Will an LG code clear if I turn it off and on?
Some do. If it comes back after five minutes off at the switchboard, the unit needs a look, and CH61 won't clear until the power's been off.
Where's the model number on an LG?
On a label on the side of the indoor unit and the outdoor unit. Send that to Phil with the code and he'll get it sorted.
Send Phil your LG code
The brand is already picked. Add the code or the light count, the model and your suburb, and Phil calls you back.
What helps Phil most
- The brand and the model number, off the sticker on the side
- Which light is flashing and how many times, or the code
- What the unit is doing, and since when
- A photo of the lights or the sticker