Fujitsu heat pump error codes and flashing lights

Every Fujitsu fault shows as a count on two lamps, and together they make a 2-digit code. The list below turns that code into the part it points to, for homes across South Auckland and Manukau.

The work
Fault-finding and repairs on heat pumps and air con, plus servicing
Phil
An electrician by trade, fixing heat pumps since 2012
Brands
Mitsubishi, Fujitsu, Panasonic, Daikin and the other main brands
Where
Manukau, Papatoetoe and Māngere down to Papakura, Drury and Beachlands
FUJITSUOPERATIONTIMERECONOMY
WHAT TO TELL PHILSOUTH AUCKLAND

Fujitsu · light flashing · send it to Phil

Brand
Fujitsu
Lights
which light, how many flashes
Model
off the side sticker

When your Fujitsu shows a fault

Two lamps flashing on your Fujitsu and a third one going fast? That's a fault code, and we see plenty of them on Fujitsu units around Manukau and South Auckland.

In New Zealand the brand now trades as GENERAL. The units and the codes haven't changed, so a unit with either name on it reads the same way.

The codes are mostly sensors, boards, fan motors and power faults, and that kind of electrical fault is what Phil trained on. Send him the two counts and the model, and he'll know where to start.

Turning the Fujitsu lamps into a code

Count the flashes on the green OPERATION lamp, then the flashes on the orange TIMER lamp. Put them side by side and you've got the code, so Operation 4 and Timer 1 is code 41. The ECONOMY lamp flashes fast the whole time.

A count of 10 stands for A, 13 for J and 15 for U, so Operation 10 and Timer 1 is A1. Units with a wired controller show the same code on the screen.

The lamps only show the fault while the unit is running, and owners have no button to bring up a stored code. If it's stopped flashing, tell Phil what you saw.

The model number

The model and serial number are on the outdoor unit, on the side or the front, and the serial starts with E, R or T.

Send it to Phil

The code or the light count, the model and what the unit is doing. Ring 0800 925 417 or use the form below.

Fujitsu codes and what they point to

Look up the two counts or the 2-digit code, starting with the group for wall, floor and ducted units.

Wall, floor and ducted units (ASTG, AGTG, ARTG)

  • Operation 1 + Timer 1 (11)Electrical

    The indoor and outdoor units have stopped talking to each other.

    Points to the cable between the units, a control board or the power supply

  • Operation 2 + Timer 3 (23)

    The indoor and outdoor units aren't a matching pair.

    Points to the indoor and outdoor combination

  • Operation 3 + Timer 1 (31)Electrical

    The power to the unit dropped out while it was running.

    Points to the power supply or a loose supply connection

  • Operation 3 + Timer 2 (32)Electrical

    The indoor board can't read the model details stored in its memory.

    Points to the indoor control board

  • Operation 3 + Timer 3 (33)Electrical

    The indoor board is getting a wrong reading of how much power the fan motor draws.

    Points to the indoor fan motor or the indoor board

  • Operation 3 + Timer 5 (35)Electrical

    The MANUAL AUTO button on the indoor unit is reading as stuck.

    Points to the MANUAL AUTO button or the display board

  • Operation 3 + Timer 9 (39)Electrical

    The power feeding the indoor fan motor isn't right.

    Points to the fan power circuit on the indoor board, or the fan motor

  • Operation 4 + Timer 1 (41)Electrical

    The sensor reading the room temperature has failed.

    Points to the room temperature sensor

  • Operation 4 + Timer 2 (42)Electrical

    The sensor in the middle of the indoor coil has failed.

    Points to the indoor coil sensor

  • Operation 4 + Timer 4 (44)Electrical

    The sensor that picks up people in the room has failed, on models fitted with one.

    Points to the human sensor

  • Operation 5 + Timer 1 (51)Electrical

    The indoor fan motor has a fault.

    Points to the indoor fan motor or the indoor board

  • Operation 5 + Timer 15 (5U)

    A catch-all fault in the indoor unit that needs testing to pin down.

    Points to somewhere in the indoor unit

  • Operation 6 + Timer 1 (61)Electrical

    The outdoor unit has found a wiring or phase problem on its supply, such as a missing or reversed phase.

    Points to the supply wiring or the cable between the units

  • Operation 6 + Timer 2 (62)Electrical

    The outdoor main board has a memory or communication fault.

    Points to the outdoor main board

  • Operation 6 + Timer 3 (63)Electrical

    The inverter that drives the compressor has a fault.

    Points to the outdoor inverter board

  • Operation 6 + Timer 4 (64)Electrical

    The circuit on the outdoor board that smooths the incoming power has a fault.

    Points to the power-factor circuit on the outdoor board, or the supply voltage

  • Operation 6 + Timer 5 (65)Electrical

    The protection circuit on the outdoor board has tripped.

    Points to the protection circuit on the outdoor board

  • Operation 6 + Timer 8 (68)Electrical

    The resistor that limits the switch-on surge is overheating.

    Points to the outdoor board or the power supply

  • Operation 6 + Timer 10 (6A)Electrical

    The two chips on the display board have stopped talking to each other.

    Points to the display board or its link to the indoor board

  • Operation 7 + Timer 1 (71)Electrical

    The sensor on the compressor's discharge pipe has failed.

    Points to the discharge sensor

  • Operation 7 + Timer 2 (72)Electrical

    The compressor's temperature sensor has failed.

    Points to the compressor sensor

  • Operation 7 + Timer 3 (73)Electrical

    The sensor on the liquid side of the outdoor coil has failed.

    Points to the outdoor coil sensor

  • Operation 7 + Timer 4 (74)Electrical

    The sensor reading the outside air has failed.

    Points to the outside air sensor

  • Operation 7 + Timer 5 (75)Electrical

    The sensor on the suction pipe back to the compressor has failed.

    Points to the suction sensor

  • Operation 7 + Timer 6 (76)Electrical

    A sensor on the 2-way or 3-way valve has failed.

    Points to the valve sensors

  • Operation 7 + Timer 7 (77)Electrical

    The heat sink sensor on the outdoor board has failed.

    Points to the heat sink sensor

  • Operation 8 + Timer 3 (83)Electrical

    The sensor on the liquid pipe has failed.

    Points to the liquid pipe sensor

  • Operation 8 + Timer 4 (84)Electrical

    The current sensor on the outdoor board has failed.

    Points to the current sensor on the outdoor board

  • Operation 9 + Timer 4 (94)Electrical

    The outdoor unit has tripped on current.

    Points to the compressor, the inverter board or the system overloading

  • Operation 9 + Timer 5 (95)Electrical

    The board can't tell where the compressor's rotor is, so it has stopped the compressor until it's fixed.

    Points to the compressor, its wiring or the inverter board

  • Operation 9 + Timer 7 (97)Electrical

    The outdoor fan motor has a fault.

    Points to the outdoor fan motor or the outdoor board

  • Operation 9 + Timer 9 (99)

    The reversing valve isn't switching between heating and cooling.

    Points to the 4-way valve or its coil

  • Operation 9 + Timer 10 (9A)Electrical

    The coil on an expansion valve has a fault.

    Points to the expansion valve coil

  • Operation 9 + Timer 15 (9U)

    A catch-all fault in the outdoor unit.

    Points to somewhere in the outdoor unit

  • Operation 10 + Timer 1 (A1)

    The pipe leaving the compressor is running too hot, often from low gas.

    Points to low gas, the expansion valve or blocked airflow

  • Operation 10 + Timer 3 (A3)

    The compressor itself is running too hot.

    Points to low gas or the compressor

  • Operation 10 + Timer 4 (A4)

    Pressure in the system has gone too high.

    Points to blocked airflow at the outdoor unit, too much gas or a valve

  • Operation 10 + Timer 5 (A5)

    Pressure on the low side has dropped too far.

    Points to low gas or a blockage

Ducted units, wired controllers and add-ons

These only show on units fitted with the part involved.

  • Operation 1 + Timer 2 (12)Electrical

    The wired controller and the indoor unit can't talk to each other.

    Points to the controller cable, the controller or the indoor board

  • Operation 1 + Timer 5 (15)

    A ducted unit's setup run, or its automatic airflow setting, hasn't finished.

    Points to the ducted airflow setup

  • Operation 1 + Timer 6 (16)Electrical

    An add-on interface board isn't connecting.

    Points to the add-on interface board or its plug

  • Operation 1 + Timer 8 (18)Electrical

    The link to an outside control system has dropped.

    Points to the external control connection

  • Operation 2 + Timer 9 (29)

    A group of units on one wired controller has a unit number problem.

    Points to the controller group wiring or settings

  • Operation 3 + Timer 10 (3A)Electrical

    The circuit on the indoor board that talks to the wired controller has a fault.

    Points to the indoor board or the wired controller

  • Operation 5 + Timer 2 (52)Electrical

    The indoor expansion valve has a fault.

    Points to the indoor expansion valve coil

  • Operation 5 + Timer 3 (53)

    The drain pump isn't getting the water away.

    Points to the drain pump, the float switch or a blocked drain

  • Operation 5 + Timer 4 (54)Electrical

    The electric air cleaner has a fault.

    Points to the air cleaner unit

  • Operation 5 + Timer 5 (55)

    The filter isn't sitting where the unit expects it.

    Points to how the filter unit is fitted

  • Operation 5 + Timer 7 (57)Electrical

    A damper isn't moving as it should.

    Points to the damper or its motor

  • Operation 5 + Timer 8 (58)

    The moving intake grille has a fault.

    Points to the intake grille or its switch

  • Operation 5 + Timer 9 (59)Electrical

    The second indoor fan motor has a fault.

    Points to indoor fan motor 2

  • Operation 5 + Timer 10 (5A)Electrical

    The third indoor fan motor has a fault.

    Points to indoor fan motor 3

  • Operation 8 + Timer 2 (82)Electrical

    A sensor on the sub-cool heat exchanger has failed, on larger outdoor units.

    Points to the sub-cool sensors

  • Operation 8 + Timer 6 (86)Electrical

    A pressure sensor or the high-pressure switch has a fault, on larger outdoor units.

    Points to the pressure sensors or the high-pressure switch

  • Operation 9 + Timer 8 (98)Electrical

    The second outdoor fan motor has a fault, on outdoor units with two fans.

    Points to outdoor fan motor 2

Multi-room systems (one outdoor unit, several indoor units)

  • Operation 2 + Timer 1 (21)

    A unit number or refrigerant address is set wrong.

    Points to the address settings

  • Operation 2 + Timer 2 (22)

    The indoor units don't suit the outdoor unit's capacity.

    Points to the indoor and outdoor combination

  • Operation 2 + Timer 4 (24)

    The number of indoor or branch units connected doesn't match the setup.

    Points to the multi-room setup

  • Operation 2 + Timer 6 (26)

    An indoor unit's address is set wrong.

    Points to the address settings

  • Operation 2 + Timer 7 (27)

    The main and secondary units aren't set up right.

    Points to the multi-room setup

  • Operation 13 + Timer 2 (J2)

    A branch box on the system has a fault.

    Points to the branch box

Fujitsu lamp patterns that aren't faults

  • Lamps blinking in turn

    OPERATION and TIMER taking turns to blink means the power went off while the unit was running. Restart it with the remote, and if a fault count shows instead, that's the one to send.

  • Lamps blinking together

    Both lamps blinking slowly at the same time is test run. It starts if someone holds the MANUAL AUTO button for 10 seconds, and START/STOP on the remote ends it.

  • Filter sign

    The filter sign is a timed reminder that comes on after a set number of running hours. It isn't a fault.

  • Defrost

    In heating the unit can pause, the indoor fan can stop and the outdoor unit steams. It lasts up to 15 minutes, then the heat comes back.

Heat Pump Doctors logo

Heat Pump Doctors, in Manukau since 2012

South Auckland Heat Pump Services is Phil of Heat Pump Doctors. He’s been fixing heat pumps and air con across South Auckland since 2012, and he’s an electrician by trade.

We find the fault first, then tell you what it is and what it’ll take before any repair goes ahead.

More about us

Fujitsu code questions

Something else? Ring 0800 925 417 or put it in the form.

How do I turn Fujitsu flashes into a code?

Count the OPERATION flashes, then the TIMER flashes, and put the two numbers together. Operation 7 and Timer 1 is 71, the sensor on the compressor's discharge pipe.

Both lamps are taking turns to blink. Is it broken?

No, that means the power went off while it was running. Restart it with the remote, and if a count shows up instead, send it to Phil.

My Fujitsu is older and the lamps don't match this list. What now?

Older Fujitsu units, from roughly before 2012, use different lamp patterns. Note which lamps flash and how many times, find the model on the outdoor unit and pass both on to Phil.

Send Phil your Fujitsu code

The brand is already picked. Add the code or the light count, the model and your suburb, and Phil calls you back.

Call 0800 925 417

What helps Phil most

  • The brand and the model number, off the sticker on the side
  • Which light is flashing and how many times, or the code
  • What the unit is doing, and since when
  • A photo of the lights or the sticker

We’re open Monday to Friday 9am to 5pm, Saturday 9am to 4pm.

    Fields are required unless marked optional. Privacy policy