Carrier heat pump error codes and flashing lights

Carrier stopped with an E, F or P code in the display window? Look it up below, then get the code to Phil in Manukau or South Auckland.

The work
Fault-finding and repairs on heat pumps and air con, plus servicing
Phil
An electrician by trade, fixing heat pumps since 2012
Brands
Mitsubishi, Fujitsu, Panasonic, Daikin and the other main brands
Where
Manukau, Papatoetoe and Māngere down to Papakura, Drury and Beachlands
CARRIERE1RUN
WHAT TO TELL PHILSOUTH AUCKLAND

Carrier · code E1 · send it to Phil

Brand
Carrier
Code
E1
Model
off the side sticker

When your Carrier shows a fault

Carrier wall heat pumps sold in New Zealand today are the Allure Plus range. When one strikes a fault in Manukau or South Auckland, it stops and puts a code in the display window on the front, or flashes the Operation lamp.

Phil starts from that code. Nearly every Carrier code points to a sensor, a board, a fan motor or the supply, and Phil's an electrician by trade.

Get the code and the model to Phil, and he'll confirm what it means on your unit.

Reading the display window and lamps on a Carrier

The Allure Plus puts the code in the display window on the front of the indoor unit. The shorter codes start with E, F or P, like E1 or P4, and newer units show a pair of letters and a number, like EH 03.

On a unit without a full display, the Operation lamp flashes a count and the Timer lamp tells you the letter. Timer off means an E code, Timer on means an F code, and Timer flashing means a P code, so count the Operation flashes and note what the Timer lamp's doing.

If the code clears by itself after 10 minutes or so, the unit has sorted it. If it comes back, that's the one to send through.

The model number

It’s on a sticker on the indoor unit. A photo of it is all Phil needs.

Send it to Phil

The code or the light count, the model and what the unit is doing. Ring 0800 925 417 or use the form below.

Carrier codes by display type

This list covers the current Carrier wall models, so send Phil your model with the code and he'll confirm what it means on that unit.

E, F and P codes

Shows in the display window on the front of the indoor unit.

  • E0Electrical

    The indoor unit can't read its memory chip, or the settings on it are bad.

    Points to the indoor circuit board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • E1Electrical

    The indoor and outdoor units have stopped talking to each other.

    Points to the wiring between the units, then a board at either end

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • E2Electrical

    The indoor board has lost the timing signal it takes from the mains.

    Points to the power supply or the indoor board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • E3Electrical

    The indoor fan isn't running at the speed the board is asking for.

    Points to the indoor fan motor, its wiring or the indoor board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • E4Electrical

    The room temperature sensor has failed open or shorted.

    Points to the room sensor, its plug or the indoor board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • E5Electrical

    The sensor on the indoor coil has failed open or shorted.

    Points to the indoor coil sensor, its plug or the indoor board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • EC

    The unit thinks it's lost refrigerant and has shut itself down.

    Points to a gas leak or blockage, or a coil sensor giving a false reading

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • F1Electrical

    The outdoor air temperature sensor has failed open or shorted.

    Points to the outdoor air sensor or the outdoor board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • F2Electrical

    The sensor on the outdoor coil has failed open or shorted.

    Points to the outdoor coil sensor or the outdoor board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • F3Electrical

    The sensor on the compressor's outlet pipe has failed open or shorted.

    Points to the discharge sensor or the outdoor board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • F4Electrical

    The outdoor unit can't read its memory chip, or the settings on it are bad.

    Points to the outdoor circuit board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • F5Electrical

    The outdoor fan isn't running at the speed the board wants.

    Points to the outdoor fan motor, its wiring or the outdoor board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • P0Electrical

    The inverter power module has tripped on a fault or too much current.

    Points to the power module, the compressor, the outdoor fan or the wiring

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • P1Electrical

    The supply voltage has gone too high or too low, and the unit has stopped to protect itself.

    Points to the mains supply or the outdoor boards

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • P2

    The top of the compressor has got too hot, so the unit has shut it down.

    Points to airflow, low gas, a blockage or the compressor's overload switch

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • P4Electrical

    The inverter can't drive the compressor properly.

    Points to the compressor or its wiring, the power module or the outdoor board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

Two-part codes (EH, EL, EC and PC)

Newer Carrier wall units show a letter pair and a number, like EH 03.

  • EC 07Electrical

    The outdoor fan is running outside its normal speed.

    Points to the outdoor fan motor, its wiring or the outdoor board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • EC 51Electrical

    The memory chip in the outdoor unit has a settings fault.

    Points to the outdoor board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • EC 52Electrical

    The outdoor coil sensor has failed open or shorted.

    Points to the outdoor coil sensor or the outdoor board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • EC 53Electrical

    The outdoor air sensor has failed open or shorted.

    Points to the outdoor air sensor or the outdoor board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • EC 54Electrical

    The sensor on the compressor's outlet pipe has failed open or shorted.

    Points to the discharge sensor or the outdoor board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • EC 56Electrical

    Another of the unit's coil sensors has failed open or shorted.

    Points to that coil sensor, its plug or its board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • EH 00Electrical

    The memory chip in the indoor unit has a settings fault. Some units show it as EH 0A.

    Points to the indoor board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • EH 02Electrical

    The indoor board isn't picking up the timing signal from the mains.

    Points to the power supply or the indoor board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • EH 03Electrical

    The indoor fan is running outside its normal speed.

    Points to the indoor fan motor, its wiring or the indoor board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • EH 0bElectrical

    The indoor main board and the display board on the front have stopped talking.

    Points to the display board, its cable or the main board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • EH 60Electrical

    The room temperature sensor has failed open or shorted.

    Points to the room sensor, its plug or the indoor board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • EH 61Electrical

    The sensor on the indoor coil has failed open or shorted.

    Points to the indoor coil sensor, its plug or the indoor board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • EH b1Electrical

    The indoor board has lost contact with an add-on board fitted to the unit.

    Points to the add-on board, its cable or the indoor board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • EL 01Electrical

    The indoor and outdoor units have stopped talking to each other.

    Points to the wiring between the units, or a board at either end

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • EL 0C

    The unit has picked up a refrigerant leak and stopped.

    Points to a gas leak or blockage, or a coil sensor giving a false reading

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • PC 00Electrical

    The inverter power module has tripped on a fault or too much current.

    Points to the power module, the compressor or the wiring

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • PC 01Electrical

    The voltage has gone too high or too low, and the unit has protected itself.

    Points to the mains supply or the outdoor boards

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • PC 02

    The compressor or the power module is running too hot, or pressure has gone too high.

    Points to airflow over the outdoor coil, the gas charge or a blockage

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • PC 03

    Pressure in the refrigerant circuit has dropped too low.

    Points to a gas leak or a blockage

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • PC 04Electrical

    The inverter can't drive the compressor properly.

    Points to the compressor or its wiring, the power module or the outdoor board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • PC 08Electrical

    The system is drawing too much current and has protected itself.

    Points to the compressor or outdoor electrics under load, or the supply

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • PC 40Electrical

    The outdoor control chip and the compressor drive chip have stopped talking.

    Points to the outdoor main board or the drive board

    Safe to try wait 10 minutes. Still there? Switch off at the power, then back on.

  • --

    On a multi-room system, this unit has asked for a mode that clashes with another indoor unit on the same outdoor unit, like one heating and one cooling.

    Points to two rooms set to opposite modes

Things a Carrier shows that aren't faults

  • dF on the display

    The outdoor coil is defrosting in heating. Heat comes back on its own, and a bit of white mist off both units afterwards is normal.

  • CL or nF flashing

    These are filter reminders. CL comes up after about 240 hours of running and nF after about 2,880. A steady CL on a unit with Active Clean means that cycle is running.

  • cF when heating starts

    The fan's holding off until the coil is warm, so it doesn't blow cold air.

  • Still running after you switch it off

    After cooling or dry mode, the unit can keep going on very low power for a while to dry the coil.

Heat Pump Doctors logo

Heat Pump Doctors, in Manukau since 2012

South Auckland Heat Pump Services is Phil of Heat Pump Doctors. He’s been fixing heat pumps and air con across South Auckland since 2012, and he’s an electrician by trade.

We find the fault first, then tell you what it is and what it’ll take before any repair goes ahead.

More about us

Carrier code questions

Something else? Ring 0800 925 417 or put it in the form.

What does EC mean on my Allure Plus?

EC means the unit thinks it's lost refrigerant and has switched itself off. A coil sensor reading wrong can set it off too, so it's worth Phil having a look at both.

My Carrier shows EH 03, not E3. Are they the same?

They point to the same thing, the indoor fan. The Allure Plus shows the shorter codes, and some newer Carrier units show the two-part kind.

What if the code goes away on its own?

A Carrier can clear a code by itself after about 10 minutes. If it comes back, write it down and send it to Phil with the model, so he knows what he's looking for before he arrives.

Send Phil your Carrier code

The brand is already picked. Add the code or the light count, the model and your suburb, and Phil calls you back.

Call 0800 925 417

What helps Phil most

  • The brand and the model number, off the sticker on the side
  • Which light is flashing and how many times, or the code
  • What the unit is doing, and since when
  • A photo of the lights or the sticker